Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Power sources for safety purposes: independent of the normal supply
VKF-17-15-012
pragmaticBIM.ch/vkf-17-15-012
A power supply for safety purposes is needed for the safety lighting of rooms, escape routes and escape signs, and for fire protection installations such as sprinkler pumps and fire-brigade lifts.
Description
It uses sources independent of the normal supply: batteries, generating sets with an independent drive, or an additional, independent and secured feed. For escape-route marking and safety lighting, the additional feed is not allowed. Not yet checkable: the model does not show which consumers are connected to what.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 7)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-013
Safety power sources: installation room at least EI 30, separation EI 60
Power sources for safety purposes and their controls are installed in fixed positions in rooms with a low fire risk. The installation room matches the fire resistance of the structure or the fire compartments, but at least EI 30; the doors are EI 30.
-
VKF-17-15-014
Distribution network for safety purposes: separate circuits, functional endurance, separation
Circuits for safety purposes are laid independently of other circuits. The distribution network is protected against fire so that functional endurance matches the intended operating time of the connected consumers.
-
VKF-17-15-015
Acceptance test of safety lighting and safety power supply
Complex projects for safety lighting and power supply for safety purposes, including escape-route marking, are submitted for approval before construction starts when the fire authority requests it. After completion, and after major extensions and changes, the installations are accepted and the test is documented.