Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Distribution network for safety purposes: separate circuits, functional endurance, separation
VKF-17-15-014
pragmaticBIM.ch/vkf-17-15-014
Circuits for safety purposes are laid independently of other circuits. The distribution network is protected against fire so that functional endurance matches the intended operating time of the connected consumers.
Description
Overcurrent protection, switches, terminals and wiring of the safety power supply are separated with fire resistance from the floor distribution boards of the general supply. Not yet checkable: the model does not represent circuits and cable routes with functional endurance.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 7)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-001
Offices, trade, schools, high-rise: escape signs and safety lighting
In office, industrial and trade buildings, school buildings, underground protective structures and high-rise buildings, exits and escape routes are marked with escape signs, and safety lighting is installed in the escape routes.
-
VKF-17-15-002
Accommodation: illuminated escape signs on safety lighting and safety lighting
In accommodation facilities, exits and escape routes are marked with escape signs on safety lighting, and safety lighting is installed in the escape routes. For remote accommodation facilities (e.g. mountain huts) the fire authority decides whether it is needed.
-
VKF-17-15-015
Acceptance test of safety lighting and safety power supply
Complex projects for safety lighting and power supply for safety purposes, including escape-route marking, are submitted for approval before construction starts when the fire authority requests it. After completion, and after major extensions and changes, the installations are accepted and the test is documented.