Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply

Safety power sources: installation room at least EI 30, separation EI 60

VKF-17-15-013 pragmaticBIM.ch/vkf-17-15-013

Power sources for safety purposes and their controls are installed in fixed positions in rooms with a low fire risk. The installation room matches the fire resistance of the structure or the fire compartments, but at least EI 30; the doors are EI 30.

Description

It is separated from the distribution boards of the general power supply with EI 60. Batteries may stand in rooms without fire hazard and get a protective box EI 30; for batteries that are not maintenance-free the ceiling area is adequately ventilated. Not yet checkable: the model does not show which rooms contain safety power sources.

Source

VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 7)