Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Safety luminaires: light the floor zone and the route to the open air
VKF-17-15-010
pragmaticBIM.ch/vkf-17-15-010
In escape and rescue routes, safety lighting adequately lights in particular the floor zone and the way to the exit to the open air. Safety luminaires mounted low above the floor have an unbreakable guard.
Description
Portable safety luminaires are allowed only in rooms entered exclusively by operating staff, and are recharged afterwards at the intended place. Not yet checkable: the model does not show which luminaires are safety luminaires or how they relate to the escape route.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 6)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-011
Safety lighting in escape routes: at least 1 lux
The illuminance of safety lighting in escape routes is at least 1 lux. Not yet checkable: the model carries no illuminance for luminaires or escape routes.
-
VKF-17-15-012
Power sources for safety purposes: independent of the normal supply
A power supply for safety purposes is needed for the safety lighting of rooms, escape routes and escape signs, and for fire protection installations such as sprinkler pumps and fire-brigade lifts.
-
VKF-17-15-013
Safety power sources: installation room at least EI 30, separation EI 60
Power sources for safety purposes and their controls are installed in fixed positions in rooms with a low fire risk. The installation room matches the fire resistance of the structure or the fire compartments, but at least EI 30; the doors are EI 30.