Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Lighting of escape signs: safety lighting, afterglow, safety power supply
VKF-17-15-008
pragmaticBIM.ch/vkf-17-15-008
Where lighting of escape signs is required, it is provided as safety lighting. Signs that are neither lit nor backlit are photoluminescent.
Description
In rooms without daylight or that can be darkened, signs on safety lighting are used. Lit and backlit signs in standby or continuous mode are fed from a safety power supply if the normal lighting fails. Not yet checkable: the model shows neither sign type, daylight nor supply.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 5)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-009
Safety lighting: at least 30 minutes, effective after 15 seconds, not switchable
Safety lighting takes effect in time when the normal lighting fails and lasts at least 30 minutes; if the general power supply fails, it is operating after 15 seconds at the latest.
-
VKF-17-15-010
Safety luminaires: light the floor zone and the route to the open air
In escape and rescue routes, safety lighting adequately lights in particular the floor zone and the way to the exit to the open air. Safety luminaires mounted low above the floor have an unbreakable guard.
-
VKF-17-15-011
Safety lighting in escape routes: at least 1 lux
The illuminance of safety lighting in escape routes is at least 1 lux. Not yet checkable: the model carries no illuminance for luminaires or escape routes.