Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply

Safety lighting: at least 30 minutes, effective after 15 seconds, not switchable

VKF-17-15-009 pragmaticBIM.ch/vkf-17-15-009

Safety lighting takes effect in time when the normal lighting fails and lasts at least 30 minutes; if the general power supply fails, it is operating after 15 seconds at the latest.

Description

Neither a main switch nor the room lighting switch affects it, and luminaires with a single battery have no switch that would interrupt their function. Central systems are divided into mutually independent groups that do not affect each other in the event of faults. Safety luminaires, switch and distribution boxes and circuits are labelled as such. Not yet checkable: the model carries neither duration, start-up time nor switching of luminaires.

Source

VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 6)