Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Safety lighting: at least 30 minutes, effective after 15 seconds, not switchable
VKF-17-15-009
pragmaticBIM.ch/vkf-17-15-009
Safety lighting takes effect in time when the normal lighting fails and lasts at least 30 minutes; if the general power supply fails, it is operating after 15 seconds at the latest.
Description
Neither a main switch nor the room lighting switch affects it, and luminaires with a single battery have no switch that would interrupt their function. Central systems are divided into mutually independent groups that do not affect each other in the event of faults. Safety luminaires, switch and distribution boxes and circuits are labelled as such. Not yet checkable: the model carries neither duration, start-up time nor switching of luminaires.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 6)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-010
Safety luminaires: light the floor zone and the route to the open air
In escape and rescue routes, safety lighting adequately lights in particular the floor zone and the way to the exit to the open air. Safety luminaires mounted low above the floor have an unbreakable guard.
-
VKF-17-15-011
Safety lighting in escape routes: at least 1 lux
The illuminance of safety lighting in escape routes is at least 1 lux. Not yet checkable: the model carries no illuminance for luminaires or escape routes.
-
VKF-17-15-012
Power sources for safety purposes: independent of the normal supply
A power supply for safety purposes is needed for the safety lighting of rooms, escape routes and escape signs, and for fire protection installations such as sprinkler pumps and fire-brigade lifts.