Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Escape signs: visibility not impaired, no confusing green
VKF-17-15-006
pragmaticBIM.ch/vkf-17-15-006
Decorations, advertising and other fittings do not impair the view of escape signs. Other illuminated signs, inscriptions and mirrors do not distract or cause confusion.
Description
Green is not used for other purposes in a way that could be mistaken for escape signs. Not yet checkable: escape signs, advertising and colours are not represented in the model.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 5)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-007
Escape signs: durable, easily recognizable, white on green
Escape signs are durable and large enough to be easily recognizable; the required size depends on the distance from which the meaning must still be clear. According to recognized standards they are rectangular or square, with white arrows and symbols on a green ground.
-
VKF-17-15-008
Lighting of escape signs: safety lighting, afterglow, safety power supply
Where lighting of escape signs is required, it is provided as safety lighting. Signs that are neither lit nor backlit are photoluminescent.
-
VKF-17-15-009
Safety lighting: at least 30 minutes, effective after 15 seconds, not switchable
Safety lighting takes effect in time when the normal lighting fails and lasts at least 30 minutes; if the general power supply fails, it is operating after 15 seconds at the latest.