Rule Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
Escape signs: durable, easily recognizable, white on green
VKF-17-15-007
pragmaticBIM.ch/vkf-17-15-007
Escape signs are durable and large enough to be easily recognizable; the required size depends on the distance from which the meaning must still be clear. According to recognized standards they are rectangular or square, with white arrows and symbols on a green ground.
Description
Not yet checkable: size and design of signs are not represented in the model.
Source
VKF-Brandschutzrichtlinie 17-15 Kennzeichnung von Fluchtwegen, Sicherheitsbeleuchtung, Sicherheitsstromversorgung (2015) (p. 5)
More rules for Fire protection directive 17-15 Escape route marking, safety lighting, safety power supply
-
VKF-17-15-008
Lighting of escape signs: safety lighting, afterglow, safety power supply
Where lighting of escape signs is required, it is provided as safety lighting. Signs that are neither lit nor backlit are photoluminescent.
-
VKF-17-15-009
Safety lighting: at least 30 minutes, effective after 15 seconds, not switchable
Safety lighting takes effect in time when the normal lighting fails and lasts at least 30 minutes; if the general power supply fails, it is operating after 15 seconds at the latest.
-
VKF-17-15-010
Safety luminaires: light the floor zone and the route to the open air
In escape and rescue routes, safety lighting adequately lights in particular the floor zone and the way to the exit to the open air. Safety luminaires mounted low above the floor have an unbreakable guard.