Rule Fire protection directive 16-15 Escape and rescue routes
Escape route with a single exit at most 35 m
VKF-16-15-002
pragmaticBIM.ch/vkf-16-15-002
Where only one exit to the outside or only one stair serves as vertical escape route, the route from the most remote point of an interior space is limited to 35 m. The model does not show whether a second, independent escape route exists, so the check reports routes above 35 m as a warning.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-003
Doors on escape routes: clear width at least 0.90 m
A door that an escape route passes through needs a clear opening width of at least 0.90 m. Depending on the use, smaller sizes are allowed, for example for doors to ancillary or small rooms.
-
VKF-16-15-004
Doors on escape routes: clear height at least 2.00 m
Doors on escape routes need a clear passage height of 2.00 m; use-specific deviations are possible. The check reads the overall door height (IfcDoor.OverallHeight): if even that is below 2.00 m, the clear height is too small.
-
VKF-16-15-005
Horizontal escape routes at least 1.20 m wide
Corridors and other horizontal escape routes are at least 1.20 m wide, measured between walls or railings. A higher occupancy can require more width.