Rule Fire protection directive 16-15 Escape and rescue routes
Doors on escape routes: clear width at least 0.90 m
VKF-16-15-003
pragmaticBIM.ch/vkf-16-15-003
A door that an escape route passes through needs a clear opening width of at least 0.90 m. Depending on the use, smaller sizes are allowed, for example for doors to ancillary or small rooms.
Description
The check reads the overall door width (IfcDoor.OverallWidth): if even that is below 0.90 m, the clear width is too small.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-004
Doors on escape routes: clear height at least 2.00 m
Doors on escape routes need a clear passage height of 2.00 m; use-specific deviations are possible. The check reads the overall door height (IfcDoor.OverallHeight): if even that is below 2.00 m, the clear height is too small.
-
VKF-16-15-005
Horizontal escape routes at least 1.20 m wide
Corridors and other horizontal escape routes are at least 1.20 m wide, measured between walls or railings. A higher occupancy can require more width.
-
VKF-16-15-006
Stairs on escape routes: width 1.20 m, winding 1.50 m
Straight stairs including landings on escape routes are at least 1.20 m wide. Winding stairs need 1.50 m and an inner tread width of at least 0.15 m.