Rule Fire protection directive 16-15 Escape and rescue routes
Record occupancy, room exits directly onto escape routes
VKF-16-15-023
pragmaticBIM.ch/vkf-16-15-023
The decisive occupancy determines the number and dimensions of escape routes and is to be recorded in writing and bindingly. Where no binding data exist (e.g. seating plans), area-based assumptions apply and may be adapted to the project.
Description
The number and width of room exits follow this occupancy. At least two thirds of the required exit width lead directly onto horizontal or vertical escape routes; at most one third may lead through an otherwise used zone (e.g. foyer, waiting room), provided the width is kept clear in operation. Not yet checkable: occupancy and zone use are not stored as typed values in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 11)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-024
Shops: circulation routes 1.2 m, main routes 1.8 m, escape streets 3.6 m
Shops must have circulation routes serving escape; where they merge, main circulation routes arise. Circulation routes are at least 1.2 m wide and main routes at least 1.8 m.
-
VKF-16-15-025
Seating: passage 0.45 m, at most 32 or 16 seats per row
In rooms with large occupancy, seats are arranged in rows and interrupted by aisles so that the exits can be reached as directly as possible. The free passage between rows is at least 0.45 m, and circulation routes are at least 1.2 m wide.
-
VKF-16-15-026
Accommodation: horizontal evacuation, hotel room doors, reception
On bed floors of accommodation [a] where sick, care-dependent or assistance-dependent people are housed, the horizontal escape routes are subdivided so that, together with the patient rooms, at least two independent fire compartments allow horizontal evacuation.