Rule Fire protection directive 16-15 Escape and rescue routes
Escape route within the use unit at most 35 m
VKF-16-15-012
pragmaticBIM.ch/vkf-16-15-012
Within a use unit the escape route may measure at most 35 m. If the exits do not lead directly outside or into a vertical escape route within these 35 m, a horizontal escape route is needed in between (e.g. a corridor with fire resistance or an access balcony).
Description
For very high rooms the fire protection authority may allow up to 50 m if several escape directions are available. Not yet checkable: use units are not clearly identified in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-013
Exit width above 200 people: 0.6 m per 100 or per 60 people
With an occupancy above 200 people, the exits together must be at least 0.6 m wide per 100 people where the route leads outside at ground level, and at least 0.6 m per 60 people where it leads over stairs. Example from the appendix: 400 people over stairs give 4.0 m total width.
-
VKF-16-15-014
External stairs: definition and protected external walls
A stair system counts as an external stair if less than half of its plan area is enclosed by external building walls and half of the facade portion bordering the outside is permanently open, with evenly distributed openings that cannot be closed.
-
VKF-16-15-015
Horizontal escape routes: lead to the vertical route, subdivided above 50 m
Horizontal escape routes lead to a vertical escape route or to a safe place outside. If they are longer than 50 m, fire separations divide them so that escape routes of similar length result.