Rule Fire protection directive 16-15 Escape and rescue routes
Doors on escape routes: clear height at least 2.00 m
VKF-16-15-004
pragmaticBIM.ch/vkf-16-15-004
Doors on escape routes need a clear passage height of 2.00 m; use-specific deviations are possible. The check reads the overall door height (IfcDoor.OverallHeight): if even that is below 2.00 m, the clear height is too small.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-005
Horizontal escape routes at least 1.20 m wide
Corridors and other horizontal escape routes are at least 1.20 m wide, measured between walls or railings. A higher occupancy can require more width.
-
VKF-16-15-006
Stairs on escape routes: width 1.20 m, winding 1.50 m
Straight stairs including landings on escape routes are at least 1.20 m wide. Winding stairs need 1.50 m and an inner tread width of at least 0.15 m.
-
VKF-16-15-007
Number of stairs as vertical escape routes by floor area
A storey without sufficient ground-level exits to the outside needs at least one vertical escape route up to 900 m² of floor area and at least two above 900 m². Rooms for more than 100 people also need two vertical escape routes unless sufficient ground-level exits exist.