Rule Fire protection directive 16-15 Escape and rescue routes
Horizontal escape routes at least 1.20 m wide
VKF-16-15-005
pragmaticBIM.ch/vkf-16-15-005
Corridors and other horizontal escape routes are at least 1.20 m wide, measured between walls or railings. A higher occupancy can require more width.
Description
The check reads the planned clear escape-route width of the space (quantitytypeescaperouteclearwidth).
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-006
Stairs on escape routes: width 1.20 m, winding 1.50 m
Straight stairs including landings on escape routes are at least 1.20 m wide. Winding stairs need 1.50 m and an inner tread width of at least 0.15 m.
-
VKF-16-15-007
Number of stairs as vertical escape routes by floor area
A storey without sufficient ground-level exits to the outside needs at least one vertical escape route up to 900 m² of floor area and at least two above 900 m². Rooms for more than 100 people also need two vertical escape routes unless sufficient ground-level exits exist.
-
VKF-16-15-008
Room exits by occupancy
The number and width of a room's exits depend on its occupancy: up to 50 people one exit of 0.90 m; up to 100 people two of 0.90 m each; up to 200 people three of 0.90 m each or two of 0.90 m and 1.20 m; more than 200 people several of at least 1.20 m each.