Rule Fire protection directive 16-15 Escape and rescue routes
Stairs on escape routes: width 1.20 m, winding 1.50 m
VKF-16-15-006
pragmaticBIM.ch/vkf-16-15-006
Straight stairs including landings on escape routes are at least 1.20 m wide. Winding stairs need 1.50 m and an inner tread width of at least 0.15 m.
Description
Some uses (e.g. housing) allow narrower stairs; those exceptions are outside this check. The check reads the clear flight width (quantitytypeclearwidth) and, for winders, the inner tread length (quantitytypetreadlengthatinnerside).
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-007
Number of stairs as vertical escape routes by floor area
A storey without sufficient ground-level exits to the outside needs at least one vertical escape route up to 900 m² of floor area and at least two above 900 m². Rooms for more than 100 people also need two vertical escape routes unless sufficient ground-level exits exist.
-
VKF-16-15-008
Room exits by occupancy
The number and width of a room's exits depend on its occupancy: up to 50 people one exit of 0.90 m; up to 100 people two of 0.90 m each; up to 200 people three of 0.90 m each or two of 0.90 m and 1.20 m; more than 200 people several of at least 1.20 m each.
-
VKF-16-15-009
Doors on escape routes open in the escape direction
Doors on escape routes open in the escape direction and can be opened quickly in that direction at any time without a key or tool. For rooms for at most 20 people the swing direction is free; the check applies only when a connected space has PeakOccupancy above 20 or no occupancy is set.