Rule Fire protection directive 16-15 Escape and rescue routes

Number of stairs as vertical escape routes by floor area

VKF-16-15-007 pragmaticBIM.ch/vkf-16-15-007

A storey without sufficient ground-level exits to the outside needs at least one vertical escape route up to 900 m² of floor area and at least two above 900 m². Rooms for more than 100 people also need two vertical escape routes unless sufficient ground-level exits exist.

Description

The check reads the storey floor area (IfcQuantityArea) and counts stairs (IfcStair) per storey; for PeakOccupancy above 100 it requires two stairs. It does not judge whether ground-level exits are enough.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)

More rules for Fire protection directive 16-15 Escape and rescue routes