Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments

Transformer rooms: separate fire compartment, at least EI 60

VKF-15-15-023 pragmaticBIM.ch/vkf-15-15-023

Rooms for transformers are built as separate fire compartments. Their enclosure matches the fire resistance of the use-related compartmentation, but at least EI 60.

Description

Supply and exhaust air openings lead directly to the open air. For other technical rooms, construction type and fire resistance depend on the type of plant, the fire hazard and the building structure. Not yet checkable: the model does not identify fire compartments or ventilation openings of these rooms.

Source

VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 16)

More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments