Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Transformer rooms: separate fire compartment, at least EI 60
VKF-15-15-023
pragmaticBIM.ch/vkf-15-15-023
Rooms for transformers are built as separate fire compartments. Their enclosure matches the fire resistance of the use-related compartmentation, but at least EI 60.
Description
Supply and exhaust air openings lead directly to the open air. For other technical rooms, construction type and fire resistance depend on the type of plant, the fire hazard and the building structure. Not yet checkable: the model does not identify fire compartments or ventilation openings of these rooms.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 16)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-001
Structure in basements at least R 60
Load-bearing elements below ground need the same fire resistance as the structure of the storeys above, and in any case R 60. Single-family houses including their basement and buildings of small dimensions are exempt.
-
VKF-15-15-002
Fire compartment walls and slabs in basements at least EI 60
Walls and slabs forming fire compartments below ground meet the requirement of their use, and at least EI 60. The check treats every wall or slab with a stated fire resistance of class EI, REI or F as forming a compartment.
-
VKF-15-15-003
Openings in fire compartment walls closed by a fire-rated closure
Doors, windows and other openings in walls that form fire compartments are closed by a fire-rated closure. EI 30 is the usual requirement; where the fire load is very small (e.g. between corridor and staircase) E 30 is enough.