Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Openings in fire compartment walls closed by a fire-rated closure
VKF-15-15-003
pragmaticBIM.ch/vkf-15-15-003
Doors, windows and other openings in walls that form fire compartments are closed by a fire-rated closure. EI 30 is the usual requirement; where the fire load is very small (e.g. between corridor and staircase) E 30 is enough.
Description
The check covers openings in walls with a fire resistance of 30 minutes or more; the element needs at least E 30.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 9)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-004
Structure: fire resistance by building height
Load-bearing elements need at least, by building height: low R 30, medium R 60, high-rise R 90. With sprinklers: low no requirement, medium R 30, high-rise R 60.
-
VKF-15-15-005
Floor slabs: fire resistance by building height
Floor slabs forming fire compartments need at least, by building height: low REI 30, medium REI 60, high-rise REI 90. With sprinklers: low EI 30, medium REI 30, high-rise REI 60.
-
VKF-15-15-006
Fire compartment walls: fire resistance by building height
Walls separating fire compartments or horizontal escape routes need at least EI 30 at low and medium height and EI 60 in high-rises (EI 30 with sprinklers). These are the lowest values of the tables; other uses partly require more.