Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Fire compartment walls and slabs in basements at least EI 60
VKF-15-15-002
pragmaticBIM.ch/vkf-15-15-002
Walls and slabs forming fire compartments below ground meet the requirement of their use, and at least EI 60. The check treats every wall or slab with a stated fire resistance of class EI, REI or F as forming a compartment.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 8)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-003
Openings in fire compartment walls closed by a fire-rated closure
Doors, windows and other openings in walls that form fire compartments are closed by a fire-rated closure. EI 30 is the usual requirement; where the fire load is very small (e.g. between corridor and staircase) E 30 is enough.
-
VKF-15-15-004
Structure: fire resistance by building height
Load-bearing elements need at least, by building height: low R 30, medium R 60, high-rise R 90. With sprinklers: low no requirement, medium R 30, high-rise R 60.
-
VKF-15-15-005
Floor slabs: fire resistance by building height
Floor slabs forming fire compartments need at least, by building height: low REI 30, medium REI 60, high-rise REI 90. With sprinklers: low EI 30, medium REI 30, high-rise REI 60.