Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Accommodation: guest rooms and technical rooms as fire compartments
VKF-15-15-020
pragmaticBIM.ch/vkf-15-15-020
In accommodation facilities, guest, inmate, patient and staff rooms, operational technical rooms, examination, treatment and laboratory areas, and technical rooms are each built as fire compartments. Not yet checkable: the model does not identify fire compartments.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 15)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-021
Car parks: fire compartments of 4800 m² or 2400 m²
Car parks form their own fire compartments. For underground car parks and closed above-ground car parks the permitted compartment area is 4800 m² if the car park has one storey or the storeys form separate compartments.
-
VKF-15-15-022
High-rise buildings: no inspection openings in safety stairwells, limit fire spread at the slab edge
In high-rise buildings, measures against fire spread are taken at every storey where the floor slab meets the external wall; they are not needed where full extinguishing-system protection is provided. Inspection openings of installation shafts are not located in safety stairwells.
-
VKF-15-15-023
Transformer rooms: separate fire compartment, at least EI 60
Rooms for transformers are built as separate fire compartments. Their enclosure matches the fire resistance of the use-related compartmentation, but at least EI 60.