Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Car parks: fire compartments of 4800 m² or 2400 m²
VKF-15-15-021
pragmaticBIM.ch/vkf-15-15-021
Car parks form their own fire compartments. For underground car parks and closed above-ground car parks the permitted compartment area is 4800 m² if the car park has one storey or the storeys form separate compartments.
Description
Where the storeys are openly connected, it is 2400 m². With an extinguishing system the areas double. For partly open car parks (at least 25 % non-closable openings in the enclosing walls) the area connected per storey without compartmentation must not exceed 9600 m². Not yet checkable: the model identifies neither fire compartments nor open wall proportions.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 15)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-001
Structure in basements at least R 60
Load-bearing elements below ground need the same fire resistance as the structure of the storeys above, and in any case R 60. Single-family houses including their basement and buildings of small dimensions are exempt.
-
VKF-15-15-022
High-rise buildings: no inspection openings in safety stairwells, limit fire spread at the slab edge
In high-rise buildings, measures against fire spread are taken at every storey where the floor slab meets the external wall; they are not needed where full extinguishing-system protection is provided. Inspection openings of installation shafts are not located in safety stairwells.
-
VKF-15-15-023
Transformer rooms: separate fire compartment, at least EI 60
Rooms for transformers are built as separate fire compartments. Their enclosure matches the fire resistance of the use-related compartmentation, but at least EI 60.