Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments

Car parks: fire compartments of 4800 m² or 2400 m²

VKF-15-15-021 pragmaticBIM.ch/vkf-15-15-021

Car parks form their own fire compartments. For underground car parks and closed above-ground car parks the permitted compartment area is 4800 m² if the car park has one storey or the storeys form separate compartments.

Description

Where the storeys are openly connected, it is 2400 m². With an extinguishing system the areas double. For partly open car parks (at least 25 % non-closable openings in the enclosing walls) the area connected per storey without compartmentation must not exceed 9600 m². Not yet checkable: the model identifies neither fire compartments nor open wall proportions.

Source

VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 15)

More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments