Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
High-rise buildings: no inspection openings in safety stairwells, limit fire spread at the slab edge
VKF-15-15-022
pragmaticBIM.ch/vkf-15-15-022
In high-rise buildings, measures against fire spread are taken at every storey where the floor slab meets the external wall; they are not needed where full extinguishing-system protection is provided. Inspection openings of installation shafts are not located in safety stairwells.
Description
Not yet checkable: the model shows neither the fire-spread barriers at the slab edge nor the location of inspection openings.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 16)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-001
Structure in basements at least R 60
Load-bearing elements below ground need the same fire resistance as the structure of the storeys above, and in any case R 60. Single-family houses including their basement and buildings of small dimensions are exempt.
-
VKF-15-15-002
Fire compartment walls and slabs in basements at least EI 60
Walls and slabs forming fire compartments below ground meet the requirement of their use, and at least EI 60. The check treats every wall or slab with a stated fire resistance of class EI, REI or F as forming a compartment.
-
VKF-15-15-023
Transformer rooms: separate fire compartment, at least EI 60
Rooms for transformers are built as separate fire compartments. Their enclosure matches the fire resistance of the use-related compartmentation, but at least EI 60.