Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Housing: dwellings as separate fire compartments
VKF-15-15-018
pragmaticBIM.ch/vkf-15-15-018
Dwellings are built as separate fire compartments. For single-family houses including their basements and an associated granny flat, no fire resistance is required of structure, walls and floors.
Description
Not yet checkable: the model does not show which walls and floors enclose a dwelling as a fire compartment.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 14)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-019
School buildings: fire compartment at most 3600 m², special rooms separate
School operations and associated uses, as well as the gymnasium with its ancillary rooms, may each be combined in one fire compartment. Without special proof the contiguous compartment area is at most 3600 m²; it includes all storeys connected without fire resistance.
-
VKF-15-15-020
Accommodation: guest rooms and technical rooms as fire compartments
In accommodation facilities, guest, inmate, patient and staff rooms, operational technical rooms, examination, treatment and laboratory areas, and technical rooms are each built as fire compartments. Not yet checkable: the model does not identify fire compartments.
-
VKF-15-15-021
Car parks: fire compartments of 4800 m² or 2400 m²
Car parks form their own fire compartments. For underground car parks and closed above-ground car parks the permitted compartment area is 4800 m² if the car park has one storey or the storeys form separate compartments.