Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
School buildings: fire compartment at most 3600 m², special rooms separate
VKF-15-15-019
pragmaticBIM.ch/vkf-15-15-019
School operations and associated uses, as well as the gymnasium with its ancillary rooms, may each be combined in one fire compartment. Without special proof the contiguous compartment area is at most 3600 m²; it includes all storeys connected without fire resistance.
Description
Special rooms such as school kitchen, cafeteria, workshops and laboratories form their own fire compartments. Not yet checkable: the model does not identify fire compartments.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 15)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-020
Accommodation: guest rooms and technical rooms as fire compartments
In accommodation facilities, guest, inmate, patient and staff rooms, operational technical rooms, examination, treatment and laboratory areas, and technical rooms are each built as fire compartments. Not yet checkable: the model does not identify fire compartments.
-
VKF-15-15-021
Car parks: fire compartments of 4800 m² or 2400 m²
Car parks form their own fire compartments. For underground car parks and closed above-ground car parks the permitted compartment area is 4800 m² if the car park has one storey or the storeys form separate compartments.
-
VKF-15-15-022
High-rise buildings: no inspection openings in safety stairwells, limit fire spread at the slab edge
In high-rise buildings, measures against fire spread are taken at every storey where the floor slab meets the external wall; they are not needed where full extinguishing-system protection is provided. Inspection openings of installation shafts are not located in safety stairwells.