Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Fire compartment walls: fire resistance by building height
VKF-15-15-006
pragmaticBIM.ch/vkf-15-15-006
Walls separating fire compartments or horizontal escape routes need at least EI 30 at low and medium height and EI 60 in high-rises (EI 30 with sprinklers). These are the lowest values of the tables; other uses partly require more.
Description
The check treats every wall with a stated fire resistance of class EI, REI or F as forming a compartment. The check derives the height category from the highest storey elevation (above 11 m medium height, above 30 m high-rise) and sprinkler protection from PsetBuildingCommon.SprinklerProtection; the top storey is the highest storey with spaces.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 11)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-007
Vertical escape routes: fire resistance by building height
The enclosure of staircases and other vertical escape routes needs at least: low height REI 30, medium height REI 60, high-rise REI 90. These values apply with sprinklers too; other uses partly require more.
-
VKF-15-15-008
Doors to staircases close automatically
Doors leading into a staircase or another vertical escape route have a door closer. Apartment doors and doors of classrooms, single offices and plant rooms are not affected.
-
VKF-15-15-009
Fire separation distance between buildings
Between neighbouring buildings, measured facade to facade: 5 m if both facades are RF1 materials on the outside; 7.5 m if one is combustible on the outside; 10 m if both are.