Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments

Fire compartment walls: fire resistance by building height

VKF-15-15-006 pragmaticBIM.ch/vkf-15-15-006

Walls separating fire compartments or horizontal escape routes need at least EI 30 at low and medium height and EI 60 in high-rises (EI 30 with sprinklers). These are the lowest values of the tables; other uses partly require more.

Description

The check treats every wall with a stated fire resistance of class EI, REI or F as forming a compartment. The check derives the height category from the highest storey elevation (above 11 m medium height, above 30 m high-rise) and sprinkler protection from PsetBuildingCommon.SprinklerProtection; the top storey is the highest storey with spaces.

Source

VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 11)

More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments