Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Doors to staircases close automatically
VKF-15-15-008
pragmaticBIM.ch/vkf-15-15-008
Doors leading into a staircase or another vertical escape route have a door closer. Apartment doors and doors of classrooms, single offices and plant rooms are not affected.
Description
Fire or smoke doors held open in operation need automatic closing in case of fire. Not yet checkable: the model does not store the door closer.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 9)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-009
Fire separation distance between buildings
Between neighbouring buildings, measured facade to facade: 5 m if both facades are RF1 materials on the outside; 7.5 m if one is combustible on the outside; 10 m if both are.
-
VKF-15-15-010
Office buildings: fire compartment at most 3600 m²
In office buildings a fire compartment covers at most 3600 m² without special proof. All storeys connected without fire resistance count together.
-
VKF-15-15-011
Penetrations through compartment components: firestop of at least 30 minutes
Openings and service penetrations in walls and floors that form fire compartments are closed with fire resistance; the firestop holds for at least 30 minutes. Allowing for thermal expansion, the recess is either filled tightly with RF1 materials or closed with a VKF-recognized firestop system rated EI 30.