Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Vertical escape routes: fire resistance by building height
VKF-15-15-007
pragmaticBIM.ch/vkf-15-15-007
The enclosure of staircases and other vertical escape routes needs at least: low height REI 30, medium height REI 60, high-rise REI 90. These values apply with sprinklers too; other uses partly require more.
Description
Not yet checkable: the model does not show which walls enclose a staircase.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 11)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-008
Doors to staircases close automatically
Doors leading into a staircase or another vertical escape route have a door closer. Apartment doors and doors of classrooms, single offices and plant rooms are not affected.
-
VKF-15-15-009
Fire separation distance between buildings
Between neighbouring buildings, measured facade to facade: 5 m if both facades are RF1 materials on the outside; 7.5 m if one is combustible on the outside; 10 m if both are.
-
VKF-15-15-010
Office buildings: fire compartment at most 3600 m²
In office buildings a fire compartment covers at most 3600 m² without special proof. All storeys connected without fire resistance count together.