Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Structure: fire resistance by building height
VKF-15-15-004
pragmaticBIM.ch/vkf-15-15-004
Load-bearing elements need at least, by building height: low R 30, medium R 60, high-rise R 90. With sprinklers: low no requirement, medium R 30, high-rise R 60.
Description
In the top storey the requirement falls away for low and medium height; in high-rises it drops there by 30 minutes. These are the lowest values of the tables (e.g. housing, office, school); other uses partly require more. Single-storey buildings, single-family houses and buildings of small dimensions are exempt. The check derives the height category from the highest storey elevation (above 11 m medium height, above 30 m high-rise) and sprinkler protection from PsetBuildingCommon.SprinklerProtection; the top storey is the highest storey with spaces.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 11)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-005
Floor slabs: fire resistance by building height
Floor slabs forming fire compartments need at least, by building height: low REI 30, medium REI 60, high-rise REI 90. With sprinklers: low EI 30, medium REI 30, high-rise REI 60.
-
VKF-15-15-006
Fire compartment walls: fire resistance by building height
Walls separating fire compartments or horizontal escape routes need at least EI 30 at low and medium height and EI 60 in high-rises (EI 30 with sprinklers). These are the lowest values of the tables; other uses partly require more.
-
VKF-15-15-007
Vertical escape routes: fire resistance by building height
The enclosure of staircases and other vertical escape routes needs at least: low height REI 30, medium height REI 60, high-rise REI 90. These values apply with sprinklers too; other uses partly require more.