Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments

Structure: fire resistance by building height

VKF-15-15-004 pragmaticBIM.ch/vkf-15-15-004

Load-bearing elements need at least, by building height: low R 30, medium R 60, high-rise R 90. With sprinklers: low no requirement, medium R 30, high-rise R 60.

Description

In the top storey the requirement falls away for low and medium height; in high-rises it drops there by 30 minutes. These are the lowest values of the tables (e.g. housing, office, school); other uses partly require more. Single-storey buildings, single-family houses and buildings of small dimensions are exempt. The check derives the height category from the highest storey elevation (above 11 m medium height, above 30 m high-rise) and sprinkler protection from PsetBuildingCommon.SprinklerProtection; the top storey is the highest storey with spaces.

Source

VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 11)