Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments

Floor slabs: fire resistance by building height

VKF-15-15-005 pragmaticBIM.ch/vkf-15-15-005

Floor slabs forming fire compartments need at least, by building height: low REI 30, medium REI 60, high-rise REI 90. With sprinklers: low EI 30, medium REI 30, high-rise REI 60.

Description

These are the lowest values of the tables; other uses partly require more. The check covers slabs above the lowest storey, without roof and base slab. The check derives the height category from the highest storey elevation (above 11 m medium height, above 30 m high-rise) and sprinkler protection from PsetBuildingCommon.SprinklerProtection; the top storey is the highest storey with spaces.

Source

VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 11)

More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments