Rule Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
Floor slabs: fire resistance by building height
VKF-15-15-005
pragmaticBIM.ch/vkf-15-15-005
Floor slabs forming fire compartments need at least, by building height: low REI 30, medium REI 60, high-rise REI 90. With sprinklers: low EI 30, medium REI 30, high-rise REI 60.
Description
These are the lowest values of the tables; other uses partly require more. The check covers slabs above the lowest storey, without roof and base slab. The check derives the height category from the highest storey elevation (above 11 m medium height, above 30 m high-rise) and sprinkler protection from PsetBuildingCommon.SprinklerProtection; the top storey is the highest storey with spaces.
Source
VKF-Brandschutzrichtlinie 15-15 Brandschutzabstände, Tragwerke, Brandabschnitte (2015) (p. 11)
More rules for Fire protection directive 15-15 Fire safety distances, load-bearing structures, fire compartments
-
VKF-15-15-006
Fire compartment walls: fire resistance by building height
Walls separating fire compartments or horizontal escape routes need at least EI 30 at low and medium height and EI 60 in high-rises (EI 30 with sprinklers). These are the lowest values of the tables; other uses partly require more.
-
VKF-15-15-007
Vertical escape routes: fire resistance by building height
The enclosure of staircases and other vertical escape routes needs at least: low height REI 30, medium height REI 60, high-rise REI 90. These values apply with sprinklers too; other uses partly require more.
-
VKF-15-15-008
Doors to staircases close automatically
Doors leading into a staircase or another vertical escape route have a door closer. Apartment doors and doors of classrooms, single offices and plant rooms are not affected.