Rule Fire protection directive 14-15 Use of building materials

Medium height: subdivide combustible facade, fire spread at most two storeys

VKF-14-15-004 pragmaticBIM.ch/vkf-14-15-004

In medium-height buildings with combustible external wall cladding or thermal insulation, the facade is subdivided structurally so that a fire spreads at most two storeys above the storey of origin before the fire brigade attacks. The fire brigade must be able to reach the facade surfaces for firefighting.

Description

Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.

Source

VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 5)