Rule Fire protection directive 14-15 Use of building materials
Ventilated facades: recognized construction, substructure RF3, fixings RF2
VKF-14-15-006
pragmaticBIM.ch/vkf-14-15-006
Ventilated facades on medium-height buildings whose cladding or insulation in the ventilated cavity is combustible are VKF-recognized or equivalent constructions. On low and medium-height buildings, rod-shaped substructures made of RF3 materials suffice.
Description
Point fixings and back-anchorages inside the insulation are made of at least RF2 materials at all building heights. Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 6)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-007
Double-skin facades made of RF1, no storey-spanning box windows
Storey-spanning double-skin facades are made of RF1 materials; combustible linear window profiles are allowed, and with additional measures combustible materials are possible. Storey-spanning box windows are not allowed.
-
VKF-14-15-008
External fabrics and films: reaction to fire, distance and position
Fabrics and films fixed on the outside are made of at least RF2 materials, on facades with an RF1 outer layer at least RF3. Combustible fabrics and films are only possible in front of facade areas without openings and fixed glazing, and keep at least 0.9 m distance in width and height from openable windows.
-
VKF-14-15-009
Materials with critical behaviour (cr) generally not usable indoors
Materials with critical behaviour (cr) are generally not usable inside buildings. Exceptions are cables, single-layer membrane facades and materials under a void-free covering with a minimum thickness of 0.5 mm (RF1), 3 mm (RF2) or 5 mm (RF3).