Room type Healthcare

Airlock

RT-CI-02 pragmaticBIM.ch/rt-ci-02

Enclosed lock or airlock for controlled passage between zones.

Room name code

RN-03-10-05 Airlock

Standard values

Interior spaces

Attribute Value Unit
PredefinedType SPACE
IsExternal Pset_SpaceCommon FALSE
LongName Airlock
Reference Pset_SpaceCommon VF
NetPlannedArea ePset_SpaceRequirement 4 m²
FloorCovering Pset_SpaceCoveringRequirements Plattenbelag
WallCovering Pset_SpaceCoveringRequirements Anstrich
CeilingCovering Pset_SpaceCoveringRequirements Metal panel ceiling
VibrationRequirements ePset_SpaceRequirement ISO Office
InteriorOrExteriorSpace INTERNAL
DesignAreaLoad ePset_SpaceRequirement 4 kN/m²
DesignPointLoad ePset_SpaceRequirement 3 kN
SecurityLevel ePset_Space Internal
WinterTemperatureMin ePset_SpaceRequirement 16 °C
WinterTemperatureMax ePset_SpaceRequirement 20 °C
SummerTemperatureMin ePset_SpaceRequirement 20 °C
SummerTemperatureMax ePset_SpaceRequirement 28 °C
RequiredIlluminance ePset_SpaceRequirement 100 lx
PeakOccupancy ePset_SpaceRequirement 2 Personen
DailyOperatingHours ePset_SpaceRequirement 12 h/Tag
OutdoorAirFlowRate ePset_SpaceRequirement 60 m³/h

Equipment

Socket outlet
  • preferred · elevation
  • required · not in clearance of · access
min. 1, 1 per 10 m² net floor area
Light switch
  • preferred · next to · access (≤ 0.3 m)
  • required · elevation
1

Openings

More room types of this use

Contact

abstract ag