Fireworks: not inside buildings; stage pyrotechnics only in designated areas, stock at most 50 kg in a room EI 30

VKF-26-15-028 pragmaticBIM.ch/vkf-26-15-028

Fireworks for entertainment must not be set off inside buildings and installations; category 4 is reserved for commercial use by qualified persons.

Description

Stage pyrotechnics of categories T1 and T2 is possible in suitable, designated areas (e.g. stages) with the authority's consent, per its instructions, classified for the application (indoor or outdoor) and used by qualified persons with a licence. It is planned before the show, tested with instructed extinguishing staff taking the surroundings into account (room height, distances to combustible material) and reported to the authority for acceptance. On site it is stored in lockable RF1 containers in rooms EI 30 with EI 30 doors, stock at most 50 kg gross; with low fire risk the rooms may serve other purposes. Not yet checkable: the model does not show category, gross mass, storage type and sales area of pyrotechnic articles.