Rule Fire protection directive 26-15 Hazardous substances
Hazardous substances from 100 kg: GHS classification, protection by type and quantity, fire protection concept before construction
VKF-26-15-001
pragmaticBIM.ch/vkf-26-15-001
The directive covers storage and handling of hazardous substances and preparations from 100 kg, unless other quantities are named. Substances are classified under the GHS, pyrotechnics under explosives law; diesel and heating oil count as combustible without classification.
Description
Protective measures depend on location, type and quantity of the substances, work processes and plant, including emptied uncleaned containers. Containers must withstand mechanical, thermal and chemical loads. For storage, a fire protection concept goes to the fire protection authority for approval before construction starts; where the hazard is especially large, risk-based protection concepts apply, e.g. free-standing single-storey non-combustible buildings. Not yet checkable: the model does not show substance classification, stored quantity, type and location of hazardous substances.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 5)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-002
No hazardous substances in escape routes or in front of exits; on-site overview, instruction, adaptation on change
Hazardous substances must not be kept in passages or drive-throughs, in horizontal or vertical escape routes, or in front of entrances and exits.
-
VKF-26-15-003
Maximum stored quantity per fire compartment: 50 t, 200 t with fire alarm, 600 t with sprinklers (by substance class)
Maximum quantities in tonnes per fire compartment depend on substance classification. For highly flammable, oxidising and self-igniting substances: 50 t without fire alarm or sprinklers, 200 t with a fire alarm, 600 t with sprinklers (2,400 t for rack storage with automatic sprinklers and foam admixture).
-
VKF-26-15-004
Rooms at fire or explosion risk: zones, pressure relief and fire compartment; storage rooms as fire compartments
Rooms are classified by fire and explosion hazard and divided into zones; type, quantity, frequency and duration of combustible gases, dusts or vapours decide.