Rule Fire protection directive 26-15 Hazardous substances

Maximum stored quantity per fire compartment: 50 t, 200 t with fire alarm, 600 t with sprinklers (by substance class)

VKF-26-15-003 pragmaticBIM.ch/vkf-26-15-003

Maximum quantities in tonnes per fire compartment depend on substance classification. For highly flammable, oxidising and self-igniting substances: 50 t without fire alarm or sprinklers, 200 t with a fire alarm, 600 t with sprinklers (2,400 t for rack storage with automatic sprinklers and foam admixture).

Description

Substances reacting with water: 50 t and 200 t, no increase with sprinklers. Combustible liquids and solids without classification and weaker oxidisers: 100 t, 400 t and 2,400 t. The values also give the maximum compartment size in m²; below 1,000 kg/m² it may at most be doubled. For mixed storage, the quantity for the most hazardous substance generally applies. Not yet checkable: the model does not show substance classification, stored quantity, type and location of hazardous substances.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 6)

More rules for Fire protection directive 26-15 Hazardous substances