Rule Fire protection directive 25-15 Ventilation systems

Escape routes: no open air routing, ventilation separate or with fire dampers

VKF-25-15-015 pragmaticBIM.ch/vkf-25-15-015

Escape routes do not replace ventilation ducts for open air routing. Compartment-forming escape routes are in principle ventilated separately from other ventilation systems; otherwise fire dampers belong in the compartment-forming walls, with storey-by-storey subdivision, separate ducts or separate systems.

Description

The dampers have duct smoke detectors or are connected to an existing fire detection system. Not yet checkable: the model does not show which ventilation system serves or crosses an escape route.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 9)