Rule Fire protection directive 25-15 Ventilation systems
Fire-case control: system switches off automatically on alarm, otherwise manual switch-off
VKF-25-15-014
pragmaticBIM.ch/vkf-25-15-014
Ventilation systems switch off automatically when fire detection or extinguishing systems, duct smoke detectors or the thermal release of fire dampers respond. Where such devices are missing, the systems can be switched off by hand at an easily accessible place.
Description
Not yet checkable: the model holds neither the control logic nor the link between detector, system and manual switch.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 8)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-015
Escape routes: no open air routing, ventilation separate or with fire dampers
Escape routes do not replace ventilation ducts for open air routing. Compartment-forming escape routes are in principle ventilated separately from other ventilation systems; otherwise fire dampers belong in the compartment-forming walls, with storey-by-storey subdivision, separate ducts or separate systems.
-
VKF-25-15-016
Kitchen extract: grease separators, RF1 ducts, separate plant rooms from EI 60
Kitchen extract ducts are RF1 (heat-resistant) and have a grease separator or filter near the extraction point. In residential buildings RF1 is enough for hood extract; after the hood and before heat recovery a VKF-recognised shut-off device is installed.
-
VKF-25-15-017
Systems with air temperature above 85 °C: RF1 ducts and safety distances
At air temperatures above 85 °C the ventilation ducts are RF1 (heat-resistant) and keep a distance to combustible material: 0.1 m up to 100 °C, 0.2 m up to 200 °C, 0.4 m up to 400 °C. With a 30-minute cladding of RF1 (heat-resistant) the distances are halved.