Rule Fire protection directive 23-15 Conveying systems

Fire-fighting lift: shaft, lobby and landing doors

VKF-23-15-003 pragmaticBIM.ch/vkf-23-15-003

Access to the fire-fighting lift is on every floor only through lobbies. Shaft and lobbies have fire resistance EI 90, fire-resistant closures and a smoke-control pressurisation system.

Description

The landing doors reach E 60, are at least 0.8 m wide and cannot be locked. The lobby measures at least 2.4 × 2.4 m. Not yet checkable: the model identifies neither fire-fighting lifts nor their lobbies and shaft walls.

Source

VKF-Brandschutzrichtlinie 23-15 Beförderungsanlagen (2015) (p. 7)