Rule Fire protection directive 23-15 Conveying systems
Lift shaft linking several fire compartments with fire resistance
VKF-23-15-001
pragmaticBIM.ch/vkf-23-15-001
Where a lift links several fire compartments, it sits in a shaft whose enclosure matches the fire resistance of the use-related compartmentation, but at least EI 30. The shaft walls run up to the roof skin; if the shaft ends below, its top closure has the same fire resistance.
Description
Where the lift links no compartments (e.g. in a vertical escape route or as a panoramic lift in an atrium), no fire resistance is required of the shaft. Not yet checkable: the model does not show which walls form a lift shaft and which compartments it links.
Source
VKF-Brandschutzrichtlinie 23-15 Beförderungsanlagen (2015) (p. 4)
More rules for Fire protection directive 23-15 Conveying systems
-
VKF-23-15-002
Lift landing doors: fire resistance by location and building type
Lift landing doors are made of RF1 building materials. Where they open directly into a usage unit, they need E 30, or E 60 under a high fire load (above 1000 MJ/m² in the rooms).
-
VKF-23-15-003
Fire-fighting lift: shaft, lobby and landing doors
Access to the fire-fighting lift is on every floor only through lobbies. Shaft and lobbies have fire resistance EI 90, fire-resistant closures and a smoke-control pressurisation system.