Rule Fire protection directive 23-15 Conveying systems
Lift landing doors: fire resistance by location and building type
VKF-23-15-002
pragmaticBIM.ch/vkf-23-15-002
Lift landing doors are made of RF1 building materials. Where they open directly into a usage unit, they need E 30, or E 60 under a high fire load (above 1000 MJ/m² in the rooms).
Description
The shaft front has the same fire resistance as its doors. In high-rise buildings the landing doors are E 30 and do not open directly into safety staircases. Not yet checkable: the model does not show whether a lift door leads directly into a usage unit; the fire load of the rooms is not stored.
Source
VKF-Brandschutzrichtlinie 23-15 Beförderungsanlagen (2015) (p. 5)
More rules for Fire protection directive 23-15 Conveying systems
-
VKF-23-15-001
Lift shaft linking several fire compartments with fire resistance
Where a lift links several fire compartments, it sits in a shaft whose enclosure matches the fire resistance of the use-related compartmentation, but at least EI 30. The shaft walls run up to the roof skin; if the shaft ends below, its top closure has the same fire resistance.
-
VKF-23-15-003
Fire-fighting lift: shaft, lobby and landing doors
Access to the fire-fighting lift is on every floor only through lobbies. Shaft and lobbies have fire resistance EI 90, fire-resistant closures and a smoke-control pressurisation system.