Rule Fire protection directive 23-15 Conveying systems

Lift landing doors: fire resistance by location and building type

VKF-23-15-002 pragmaticBIM.ch/vkf-23-15-002

Lift landing doors are made of RF1 building materials. Where they open directly into a usage unit, they need E 30, or E 60 under a high fire load (above 1000 MJ/m² in the rooms).

Description

The shaft front has the same fire resistance as its doors. In high-rise buildings the landing doors are E 30 and do not open directly into safety staircases. Not yet checkable: the model does not show whether a lift door leads directly into a usage unit; the fire load of the rooms is not stored.

Source

VKF-Brandschutzrichtlinie 23-15 Beförderungsanlagen (2015) (p. 5)