Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Safety stairwells: smoke-protection pressurization system with overpressure against the lock
VKF-21-15-007
pragmaticBIM.ch/vkf-21-15-007
Stair enclosures of safety stairwells that are not reached on every storey through permanently open access balconies or forecourts get a smoke-protection pressurization system. The stair enclosure holds a higher overpressure than the lock.
Description
The protected areas are separate fire compartments; the system starts automatically on fire detectors, can be switched on and off by hand and acts only in purge mode when started by hand. Fire-brigade lift shafts need a performance proof. Not yet checkable: the model holds no trigger and control points of the system and no power source for safety purposes.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 8)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-008
Functional integrity of plant parts for at least 30 minutes
The system follows the state of the art and is built, sized and maintained so that it is effective and ready for operation at all times.
-
VKF-21-15-009
Exhaust openings: highest point, on façades evenly on two opposite sides
Exhaust openings are placed so that effective smoke clearance is possible without danger to people and buildings, at the highest point of the room, for example in the roof or in the ceiling or roof zone of the façades.
-
VKF-21-15-010
Hot-gas fans: temperature resistance and installation room of at least EI 30
Suitable hot-gas fans are used to extract the smoke gases; they withstand at least 400 °C for the required operating time, in compartments with a water-based extinguishing system and in vertical escape routes at least 200 °C.