Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Functional integrity of plant parts for at least 30 minutes
VKF-21-15-008
pragmaticBIM.ch/vkf-21-15-008
The system follows the state of the art and is built, sized and maintained so that it is effective and ready for operation at all times.
Description
All plant parts are made of suitable materials and withstand the stresses; their functional integrity lasts for the fire resistance period of the use-related compartmentation, but at least 30 minutes. This does not raise the requirements for the structure or the compartmentation. Not yet checkable: the model does not show the functional duration of plant parts or the fire resistance of the enclosure.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 8)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-009
Exhaust openings: highest point, on façades evenly on two opposite sides
Exhaust openings are placed so that effective smoke clearance is possible without danger to people and buildings, at the highest point of the room, for example in the roof or in the ceiling or roof zone of the façades.
-
VKF-21-15-010
Hot-gas fans: temperature resistance and installation room of at least EI 30
Suitable hot-gas fans are used to extract the smoke gases; they withstand at least 400 °C for the required operating time, in compartments with a water-based extinguishing system and in vertical escape routes at least 200 °C.
-
VKF-21-15-011
Smoke-extraction ducts and dampers: fire resistance of the crossed compartment, dampers at least EI 30
Shafts and ducts withstand the expected stresses and prevent fire and smoke spread when hot fire gases are extracted; length expansion is taken up by fixed points and compensators, and plastic anchors are not permitted for exhaust ducts.