Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Systems with performance proof for large offices, occupancies, sales areas and atria
VKF-21-15-006
pragmaticBIM.ch/vkf-21-15-006
A smoke and heat exhaust system with performance proof is needed for open-connected multi-storey office compartments above 3,600 m², rooms with over 2,000 people, shops with extinguishing system from 7,200 m² (single-storey) or 3,600 m² (multi-storey), and atria with an escape route or over 2,400 m² floor area.
Description
The proof itself follows the directive on verification procedures. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 8)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-007
Safety stairwells: smoke-protection pressurization system with overpressure against the lock
Stair enclosures of safety stairwells that are not reached on every storey through permanently open access balconies or forecourts get a smoke-protection pressurization system. The stair enclosure holds a higher overpressure than the lock.
-
VKF-21-15-008
Functional integrity of plant parts for at least 30 minutes
The system follows the state of the art and is built, sized and maintained so that it is effective and ready for operation at all times.
-
VKF-21-15-009
Exhaust openings: highest point, on façades evenly on two opposite sides
Exhaust openings are placed so that effective smoke clearance is possible without danger to people and buildings, at the highest point of the room, for example in the roof or in the ceiling or roof zone of the façades.