Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Purge ventilation of vertical escape routes from three basements
VKF-21-15-005
pragmaticBIM.ch/vkf-21-15-005
Vertical escape routes of buildings with three or more basements get purge ventilation. The fire protection concept sets how many escape routes are purged; every use unit reaches the purged escape route by a safe horizontal access.
Description
Fresh air enters at the fire brigade access level and, together with the lowest exhaust opening, purges the whole escape route. Not yet checkable: the model shows neither exhaust openings nor their free geometric area at the stairwell.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 7)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-006
Systems with performance proof for large offices, occupancies, sales areas and atria
A smoke and heat exhaust system with performance proof is needed for open-connected multi-storey office compartments above 3,600 m², rooms with over 2,000 people, shops with extinguishing system from 7,200 m² (single-storey) or 3,600 m² (multi-storey), and atria with an escape route or over 2,400 m² floor area.
-
VKF-21-15-007
Safety stairwells: smoke-protection pressurization system with overpressure against the lock
Stair enclosures of safety stairwells that are not reached on every storey through permanently open access balconies or forecourts get a smoke-protection pressurization system. The stair enclosure holds a higher overpressure than the lock.
-
VKF-21-15-008
Functional integrity of plant parts for at least 30 minutes
The system follows the state of the art and is built, sized and maintained so that it is effective and ready for operation at all times.