Rule Fire protection directive 21-15 Smoke and heat exhaust systems

Purge ventilation of vertical escape routes from three basements

VKF-21-15-005 pragmaticBIM.ch/vkf-21-15-005

Vertical escape routes of buildings with three or more basements get purge ventilation. The fire protection concept sets how many escape routes are purged; every use unit reaches the purged escape route by a safe horizontal access.

Description

Fresh air enters at the fire brigade access level and, together with the lowest exhaust opening, purges the whole escape route. Not yet checkable: the model shows neither exhaust openings nor their free geometric area at the stairwell.

Source

VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 7)

More rules for Fire protection directive 21-15 Smoke and heat exhaust systems

Contact

abstract ag

Imprint · Picassoplatz 4, 4052 Basel