Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Systems without performance proof: system type and sizing by use
VKF-21-15-002
pragmaticBIM.ch/vkf-21-15-002
For systems without performance proof the directive sets, per use, position and area, which system type is permitted: smoke clearance with fire-brigade fans, mechanical or natural systems. Sizing follows air-change rates by room height or supply and exhaust areas as a percentage of the compartment area.
Description
Restrictions or exclusions apply in basements and for atria with an escape route. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 6)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-003
Vertical escape routes: exhaust opening at the top, directly outdoors
Vertical escape routes get exhaust openings at the top leading directly outdoors: in low and medium-height buildings for accommodation, large occupancy and shops, in medium-height buildings for residential, office, industrial, commercial and school buildings and car parks, unless every storey has ventilation sashes...
-
VKF-21-15-004
Stairwell exhaust opening: 0.5 m² free, operable from the entrance level
The free geometric ventilation area of the exhaust opening at a vertical escape route is at least 0.5 m². It can be put into operation from the entrance level, and it stays operational during a power failure.
-
VKF-21-15-005
Purge ventilation of vertical escape routes from three basements
Vertical escape routes of buildings with three or more basements get purge ventilation. The fire protection concept sets how many escape routes are purged; every use unit reaches the purged escape route by a safe horizontal access.