Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Vertical escape routes: exhaust opening at the top, directly outdoors
VKF-21-15-003
pragmaticBIM.ch/vkf-21-15-003
Vertical escape routes get exhaust openings at the top leading directly outdoors: in low and medium-height buildings for accommodation, large occupancy and shops, in medium-height buildings for residential, office, industrial, commercial and school buildings and car parks, unless every storey has ventilation sashes...
Description
Vertical escape routes get exhaust openings at the top leading directly outdoors: in low and medium-height buildings for accommodation, large occupancy and shops, in medium-height buildings for residential, office, industrial, commercial and school buildings and car parks, unless every storey has ventilation sashes to the outdoors with at least 0.3 m² geometric area. Not yet checkable: the model shows neither exhaust openings nor their free geometric area at the stairwell.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 7)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-004
Stairwell exhaust opening: 0.5 m² free, operable from the entrance level
The free geometric ventilation area of the exhaust opening at a vertical escape route is at least 0.5 m². It can be put into operation from the entrance level, and it stays operational during a power failure.
-
VKF-21-15-005
Purge ventilation of vertical escape routes from three basements
Vertical escape routes of buildings with three or more basements get purge ventilation. The fire protection concept sets how many escape routes are purged; every use unit reaches the purged escape route by a safe horizontal access.
-
VKF-21-15-006
Systems with performance proof for large offices, occupancies, sales areas and atria
A smoke and heat exhaust system with performance proof is needed for open-connected multi-storey office compartments above 3,600 m², rooms with over 2,000 people, shops with extinguishing system from 7,200 m² (single-storey) or 3,600 m² (multi-storey), and atria with an escape route or over 2,400 m² floor area.