Rule Fire protection directive 20-15 Fire alarm systems

Monitoring extent: full monitoring, partial monitoring over whole fire compartments

VKF-20-15-005 pragmaticBIM.ch/vkf-20-15-005

Fire alarm systems should be designed as full monitoring and then cover entire buildings and installations, except expressly exempted rooms separated with fire resistance.

Description

Partial monitoring covers at least the escape routes and rooms with increased fire risk and always extends over a whole fire compartment; the fire protection authority can extend it to further compartments. Not yet checkable: the model holds detectors only as a device with location, without detector zone, monitored extent, mounting height and system.

Source

VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 5)