Rule Fire protection directive 20-15 Fire alarm systems
Monitoring extent: full monitoring, partial monitoring over whole fire compartments
VKF-20-15-005
pragmaticBIM.ch/vkf-20-15-005
Fire alarm systems should be designed as full monitoring and then cover entire buildings and installations, except expressly exempted rooms separated with fire resistance.
Description
Partial monitoring covers at least the escape routes and rooms with increased fire risk and always extends over a whole fire compartment; the fire protection authority can extend it to further compartments. Not yet checkable: the model holds detectors only as a device with location, without detector zone, monitored extent, mounting height and system.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 5)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-006
Areas that may be exempted from monitoring
Exemptions are possible, among others, for installation shafts that are inaccessible or free of ignition hazards, wet rooms without combustible stock, lift shafts with a separate machine room, residential areas separated as a fire compartment, cold rooms up to 50, 200 or 600 m² depending on insulation and...
-
VKF-20-15-007
Fire-brigade control and indicating unit at a safe, easily accessible location
Fire-brigade control and indicating units of systems with more than one detector zone stand at a safe location that is easily accessible for the fire brigade, in the escape route or at the fire-brigade access. The operating-state indication is in the immediate vicinity, and unobstructed access is ensured.
-
VKF-20-15-008
Alerting: internal and external alarm, delays of at most 3 and 5 minutes
Every response triggers an internal and an external alarm; the external one goes directly to the public fire alarm receiving point. Switch-offs and faults are signalled visually and audibly and forwarded to a permanently staffed point.