Rule Fire protection directive 20-15 Fire alarm systems
Shops: manual call points added to the sprinkler system; large occupancy on request
VKF-20-15-004
pragmaticBIM.ch/vkf-20-15-004
In shops the sprinkler system is supplemented with manual call points; in sub-areas or individual rooms a fire alarm system is installed where needed to activate technical fire protection equipment. For rooms with large occupancy the fire protection authority can require a fire alarm system.
Description
Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 5)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-005
Monitoring extent: full monitoring, partial monitoring over whole fire compartments
Fire alarm systems should be designed as full monitoring and then cover entire buildings and installations, except expressly exempted rooms separated with fire resistance.
-
VKF-20-15-006
Areas that may be exempted from monitoring
Exemptions are possible, among others, for installation shafts that are inaccessible or free of ignition hazards, wet rooms without combustible stock, lift shafts with a separate machine room, residential areas separated as a fire compartment, cold rooms up to 50, 200 or 600 m² depending on insulation and...
-
VKF-20-15-007
Fire-brigade control and indicating unit at a safe, easily accessible location
Fire-brigade control and indicating units of systems with more than one detector zone stand at a safe location that is easily accessible for the fire brigade, in the escape route or at the fire-brigade access. The operating-state indication is in the immediate vicinity, and unobstructed access is ensured.