In accommodation of category a a fire alarm system with full monitoring is required.

Description

In categories b and c this applies for two storeys and more than 50 accommodated persons, and for three or more storeys and more than 30 accommodated persons; for low-rise buildings with an extinguishing-system concept it can be omitted. Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.

Source

VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 4)