Rule Fire protection directive 20-15 Fire alarm systems
Industry, commerce, offices: monitoring when compartments are exceeded, smouldering fires or ban on water
VKF-20-15-002
pragmaticBIM.ch/vkf-20-15-002
For industrial, commercial and office buildings the fire protection authority can require monitoring if the permitted compartment sizes are exceeded and the system makes sense for the current use, if slowly developing fires such as smouldering fires are expected, or if water must not be used as extinguishing agent.
Description
Not yet checkable: the model does not show use, occupancy, number of storeys and compartment size per fire compartment.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 4)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-003
Accommodation: fire alarm system with full monitoring by category, number of storeys and persons
In accommodation of category a a fire alarm system with full monitoring is required.
-
VKF-20-15-004
Shops: manual call points added to the sprinkler system; large occupancy on request
In shops the sprinkler system is supplemented with manual call points; in sub-areas or individual rooms a fire alarm system is installed where needed to activate technical fire protection equipment. For rooms with large occupancy the fire protection authority can require a fire alarm system.
-
VKF-20-15-005
Monitoring extent: full monitoring, partial monitoring over whole fire compartments
Fire alarm systems should be designed as full monitoring and then cover entire buildings and installations, except expressly exempted rooms separated with fire resistance.